Monitoring of water for injection
Specific Test
|
Guideline
| |
USP
|
EP
| |
Appearance
|
NA
|
Clear Colorless
|
BET
|
Less than 0.25 EU/mL
|
less than 0.25 IU/mL
|
Conductivity
|
As per Table given in respective Monograph
|
As per Table given in respective Monograph
(below table given for reference only ) |
pH
|
pH 5.0-7.0
|
pH 5.0-7.0
|
TOC
|
500 ppb
|
Max. 0.5 mg/L
|
Microbiological monitoring
|
Action level 10 cfu/100mL (sample vol-100mL, membrane filtration method, minimum 30-35° for 48-72 hrs)
|
R2A (Sample volume 200 mL, Action level 10cfu/100mL, incubation condition not less than 5 days at 30-35°C)
|
Nitrate
|
NA
|
Max. 0.2 ppm
|
EP Table for WFI
Monitoring of Pure Steam condensate
Specific Test
|
Guideline
| |
USP
|
EP
| |
Appearance
|
NA
|
|
BET
|
Less than 0.25 EU/mL
|
--
|
Conductivity
|
As per Table
|
--
|
pH
|
pH 5.0-7.0
|
--
|
TOC
|
500 ppb
|
--
|
Microbiological monitoring
|
Action level 10 cfu/100mL (sample vol-100mL, membrane filtration method, minimum 30-35° for 48-72 hrs)
|
--
|
Nitrate
|
NA
|
--
|
Monitoring of Purified water
Specific Test
|
Guideline
| ||
USP
|
EP
|
Schedule
M
| |
Appearance
|
NA
|
Clear
colorless
|
NA
|
BET
|
NA
|
NA
|
NA
|
Conductivity
|
As per Table given in respective Monograph
|
As per Table given in respective Monograph
(below table given for reference only ) |
NA
|
pH
|
pH
5.0-7.0
|
pH
5.0-7.0
|
NA
|
TOC
|
500
ppb
|
0.5
mg/L (Alternate oxidizable test)
|
NA
|
Microbiological monitoring
|
Action
level 100 cfu/mL, sample volume 1 mL, pour-plate method or membrane filtration
method, minimum 48-72 hrs. 30-35°C
|
R2A
(Sample volume 10 mL, Action level 100cfu/mL, incubation condition not less
than 5 days at 30-35°C)
|
100
cfu/mL, Pathogen testing-E.coli, S.aureus, Salmonella and
p.aeruginosa-absence
|
Nitrate
|
NA
|
Max.
0.2 ppm
|
NA
|
Heavy metal
|
NA
|
Max.
0.1 ppm if conductivity 1.3ms/cm
|
EP Table for Purified water
Note: Please verify above details with respective Pharmacopeal monograph/Guideline/regulation.
Monitoring of Potable water
Specific Test | Guideline |
Schedule M | |
Appearance | NA |
BET | NA |
Conductivity | NA |
pH | NA |
TOC | NA |
Microbiological monitoring | Not more than 500cfu/mL, Pathogen testing-E.coli, S.aureus, Salmonella and p.aeruginosa |
Nitrate | NA |
Monitoring of Raw water/Bore well water
In-house / as per Water system Requirement
As per USP<1231 b=""> SOURCE
OR FEED WATER CONSIDERATIONS
To ensure adherence to certain minimal chemical and
microbiological quality standards, water used in the production of drug
substances or as source or feed water for the preparation of the various types
of purified waters must meet the requirements of the National Primary Drinking
Water Regulations (NPDWR) (40 CFR 141) issued by the U.S. Environmental
Protection Agency (EPA) or the drinking water regulations of the European Union
or Japan, or the WHO drinking water guidelines. Limits on the types and
quantities of certain organic and inorganic contaminants ensure that the water
will contain only small, safe quantities of potentially objectionable chemical
species. Therefore, water pretreatment systems will only be challenged to
remove small quantities of these potentially difficult-to-remove chemicals.
Also, control of objectionable chemical contaminants at the source-water stage
eliminates the need to specifically test for some of them (e.g.,
trihalomethanes and heavy metals) after the water has been further purified.
Microbiological requirements of drinking water ensure the absence
of coliforms, which, if determined to be of fecal origin, may indicate the
potential presence of other potentially pathogenic microorganisms and viruses
of fecal origin. Meeting these microbiological requirements does not rule out
the presence of other microorganisms, which could be considered undesirable if
found in a drug substance or formulated product.
To accomplish microbial control, municipal water authorities add
disinfectants to drinking water. Chlorine-containing and other oxidizing
substances have been used for many decades for this purpose and have generally
been considered to be relatively innocuous to humans. However, these oxidants
can interact with naturally occurring organic matter to produce disinfection
by-products (DBPs), such as trihalomethanes (THMs, including chloroform,
bromodichloromethane, and dibromochloromethane) and haloacetic acids (HAAs,
including dichloroacetic acid and trichloroacetic acid). The levels of DBPs
produced vary with the level and type of disinfectant used and the levels and
types of organic materials found in the water, which can vary seasonally.
Because high levels of DBPs are considered a health hazard in
drinking water, drinking water regulations mandate their control to generally
accepted nonhazardous levels. However, depending on the unit operations used
for further water purification, a small fraction of the DBPs in the starting
water may carry over to the finished water. Therefore, the importance of having
minimal levels of DBPs in the starting water, while achieving effective
disinfection, is important.
DBP levels in drinking water can be minimized by using
disinfectants such as ozone, chloramines, or chlorine dioxide. Like chlorine,
their oxidative properties are sufficient to damage some pretreatment unit
operations and must be removed early in the pretreatment process. The complete
removal of some of these disinfectants can be problematic. For example,
chloramines may degrade during the disinfection process or during pretreatment
removal, thereby releasing ammonia, which in turn can carry over to the
finished water. Pretreatment unit operations must be designed and operated to
adequately remove the disinfectant, drinking water DBPs, and objectionable
disinfectant degradants. A serious problem can occur if unit operations
designed to remove chlorine were, without warning, challenged with
chloramine-containing drinking water from a municipality that had been mandated
to cease use of chlorine disinfection to comply with ever-tightening EPA
Drinking Water THM specifications. The dechlorination process might
incompletely remove the chloramine, which could irreparably damage downstream
unit operations, but also the release of ammonia during this process might
carry through pretreatment and prevent the finished water from passing
compendial conductivity specifications. The purification process must be
reassessed if the drinking water disinfectant is changed, emphasizing the need
for a good working relationship between the pharmaceutical water manufacturer
and the drinking water provider.
No comments:
Post a Comment